The store will not work correctly when cookies are disabled.
JavaScript seems to be disabled in your browser. For the best experience on our site, be sure to turn on Javascript in your browser.
Fan BD-V140-6-2.0HP E15 46200m³ 400-3-50 assembled Basic data Montiert Mounted Type Installation at a wall
Rated values Phases 3 Ph Nominal frequency [Hz] 50 Hz Control Not controllable
Classification IP protection rating IP55 Certifications CE Insulation class (DIN EN 60085) F Efficiency rating (ErP) E15
Dimensions Width 1480 mm Height 1480 mm Total depth 548 mm Diameter 1375 mm
Rated values 50 Hz Elektrische Nennleistung 1.55 kW Nominal voltage delta connection 230 V Nominal voltage star connection 400 V Voltage tolerance -20 - 10 % Nominal current delta connection 5,4 A Nominal current star connection 3,2 A Speed 535 U/min Ambient temperature -25 - 40 °C Sound power level Lw 88 dB Sound pressure level Lp 63 dB
Volumetric flow rate 50 Hz Characteristic curve – 0 Pa 46213 m³/h Characteristic curve – 10 Pa 44985 m³/h Characteristic curve – 20 Pa 43654 m³/h Characteristic curve – 30 Pa 42360 m³/h Characteristic curve – 40 Pa 41024 m³/h Characteristic curve – 50 Pa 39384 m³/h Characteristic curve – 60 Pa 37611 m³/h Characteristic curve – 70 Pa 35943 m³/h Characteristic curve – 80 Pa 34090 m³/h Characteristic curve – 90 Pa 31929 m³/h Characteristic curve – 100 Pa 29468 m³/h Characteristic curve – 110 Pa 26876 m³/h
Spec. power 50 Hz Characteristic curve – 0 Pa 33.4 W/(1000m³/h) Characteristic curve – 10 Pa 35.4 W/(1000m³/h) Characteristic curve – 20 Pa 37.9 W/(1000m³/h) Characteristic curve – 30 Pa 40.8 W/(1000m³/h) Characteristic curve – 40 Pa 43.8 W/(1000m³/h) Characteristic curve – 50 Pa 46.8 W/(1000m³/h) Characteristic curve – 60 Pa 50.4 W/(1000m³/h) Characteristic curve – 70 Pa 54.5 W/(1000m³/h) Characteristic curve – 80 Pa 58.9 W/(1000m³/h) Characteristic curve – 90 Pa 63.6 W/(1000m³/h) Characteristic curve – 100 Pa 69.5 W/(1000m³/h) Characteristic curve – 110 Pa 76.9 W/(1000m³/h)
Illustrations may show accessories that are not included in the scope of delivery.
Due to constant further development of our products, illustrations and technical data may deviate slightly. Errors and omissions excepted.