The store will not work correctly when cookies are disabled.
JavaScript seems to be disabled in your browser. For the best experience on our site, be sure to turn on Javascript in your browser.
Fan 4D50-Q 8600m³ 400V 410W 0.9A Basic data Montiert Mounted Type Installation at a wall
Rated values Phases 3 Ph Nominal frequency [Hz] 50 Hz Control Frequency converter / Transformer
Classification IP protection rating IP55 Certifications CE Insulation class (DIN EN 60085) F Efficiency rating (ErP) E20
Rated values 50 Hz Elektrische Nennleistung 0.41 kW Nominal voltage delta connection 230 V Nominal voltage star connection 400 V Nominal current delta connection 1,9 A Nominal current star connection 1,1 A Speed 1415 U/min Ambient temperature -25 - 40 °C Sound power level Lw 80 dB Sound pressure level Lp 69 dB
Volumetric flow rate 50 Hz Characteristic curve – 0 Pa 8600 m³/h Characteristic curve – 10 Pa 8400 m³/h Characteristic curve – 20 Pa 8200 m³/h Characteristic curve – 30 Pa 8000 m³/h Characteristic curve – 40 Pa 7800 m³/h Characteristic curve – 50 Pa 7550 m³/h Characteristic curve – 60 Pa 7300 m³/h Characteristic curve – 70 Pa 7050 m³/h Characteristic curve – 80 Pa 6750 m³/h Characteristic curve – 90 Pa 6450 m³/h Characteristic curve – 100 Pa 6100 m³/h Characteristic curve – 110 Pa 5550 m³/h
Spec. power 50 Hz Characteristic curve – 0 Pa 47.8 W/(1000m³/h) Characteristic curve – 10 Pa 50.2 W/(1000m³/h) Characteristic curve – 20 Pa 52.3 W/(1000m³/h) Characteristic curve – 30 Pa 54.6 W/(1000m³/h) Characteristic curve – 40 Pa 57.1 W/(1000m³/h) Characteristic curve – 50 Pa 59.7 W/(1000m³/h) Characteristic curve – 60 Pa 62.2 W/(1000m³/h) Characteristic curve – 70 Pa 65.2 W/(1000m³/h) Characteristic curve – 80 Pa 68.1 W/(1000m³/h) Characteristic curve – 90 Pa 71.3 W/(1000m³/h) Characteristic curve – 100 Pa 75.3 W/(1000m³/h) Characteristic curve – 110 Pa 80.8 W/(1000m³/h)
Illustrations may show accessories that are not included in the scope of delivery.
Due to constant further development of our products, illustrations and technical data may deviate slightly. Errors and omissions excepted.